Calibration, automation and control of a Hall effect flow sensor for a distillation column

Authors

DOI:

https://doi.org/10.33448/rsd-v11i12.34359

Keywords:

LabView; Arduino; RSM; IDE.

Abstract

Flow is one of the essential process variables in distillation plants, and its constant measurement and control are necessary to achieve the best performance. This work aims to guarantee the process of automation, control, and calibration of a flow measurement instrument in an experimental distillation plant. A program was created in the Arduino IDE to determine the flowmeter coefficient, with a flow adjusted (manually) in the range of 0.3 L/min (indicated by the serial), measuring the actual flow rate with the aid of a 500 mL beaker, allowing the pre-defined flow rate to fill the beaker with the aid of a hose for 1 minute. With the coefficient defined for the meter (model YF-S401), five flows were chosen, starting at 0.25 L/min to 1.25 L/min. With the help of the IDE and Labview, a VI (Virtual Instrument) was created combining Labview/LINX with the help of the VISA (Virtual Instrument Software Architecture) tool. In both parts of the experiment, surface response (assisted by the STATISTICA 10 software) was used for the relationship between frequency, pulse, and flow. After the results obtained in the manual experiment and the automated experiment, the correlations obtained and the surface responses found to suggest an effective response of the integration of LINX and VISA for the measurement of flow, besides confirming the calibration (because the program corrects the error using the correlations). It is possible to state that the developed program can be integrated into a more complete automation system.

References

Barbosa, C. C. (2018). Sistemas de medição de energia elétrica visando aplicação em identificação e prevenção de falhas.

Barbosa, C. M. D., Rodrigues, C. V., Pettenon, D. A., & de Queiroz, T. M. (2018). Automação de um processo alternativo da pasteurização do leite utilizando ação de controle on-off. Revista de Engenharia e Tecnologia, 10(1), áginas-41.

Cavalcanti, G. O., & dos Santos, M. R. F. (2021). Parametrização Remota de Medidores de Vazão Eletromagnético. Revista de Engenharia e Pesquisa Aplicada, 6(4), 10-18.

Chichanoski, G. (2018). Desenvolvimento de instrumentação eletrônica com FPGA: vazão e temperatura (Bachelor's thesis, Universidade Tecnológica Federal do Paraná).

Cosimato, B. (2022). Medidor de vazão eletromagnético: suas aplicações para soluções aquosas.

Costa Neto, E., Lima, M. D., & Rolim, T. L. (2021). Calibração de hidrômetro para água fria de vazão nominal de 1, 5 m 3/h. Engenharia Sanitaria e Ambiental, 26, 793-803.

De Camargos, A. F. P., dos Santos, C. R. B., da Silva, F. D., Kai, B. H. D., & Vieira, V. (2022). Produto educacional: automação residencial com uso de Arduino e IoT. Research, Society and Development, 11(6), e8311628882-e8311628882.

Delmée, G. J. (2003). Manual de medição de vazão. Editora Blucher.

Fezari, M., & Al Dahoud, A. (2018). Integrated development environment “IDE” for Arduino. WSN applications, 1-12.

Hasanusta, K., Serteller, N. F. O., & Birbir, Y. (2016). The optimal hall sensor’s position for brushless direct current machine: experimental study. Rev. Téc. Ing. Univ. Zulia, 39(1), 218-225.

Horigoshi, F. M., & Costa, E. J. X. (2016). Uso de sensor efeito Hall para medição da vazão de fluidos no processo de produção de palatabilizantes a base de proteína animal em escala piloto.

Leong, W. Y., Soon, C. F., Wong, S. C., & Tee, K. S. (2016). Development of an electronic aerosol system for generating microcapsules. Jurnal Teknologi, 78(5-7).

Matos, B. C. D. S., & Lima, M. C. D. (2022). Efeito Faraday: entre a atividade óptica natural e a teoria dos elétrons. Revista Brasileira de Ensino de Física, 44.

Neto, L. R. P., de Mello, F. M., da Silva, A. M. B., Dias, M. C., Teixeira, E. P., & Zuffi, F. R. (2022). Controle avançado aplicado a colunas de destilação. Brazilian Journal of Development, 8(6), 44774-44780.

Parra Sejas, M. Z. (2016). Desenvolvimento de uma bancada gravimétrica automática para calibração de medidores de vazão com diferentes fluidos.

Ribeiro, L. H., Oliveira, A. F., & Rubinger, R. M. (2021). Instrumentação para medidas de mobilidade eletrônica e concentração de portadores em amostras semicondutoras, pelo método de van der Pauw. Research, Society and Development, 10(6), e41310615229-e41310615229.

Sales, J. P., Ferreira, I. S., & Gross, M. A. (2021). Proposta de Automação do Observatório Astronômico Luiz Cruls. Physicae Organum-Revista dos Estudantes de Física da UnB, 7(2), 150-163.

Santos, N. S. D. (2019). Simulação dinâmica de uma coluna de destilação.

Sousa, D. F. M., de Negreiro Neto, L. G., de Lima, I. F., Oliveira, N. W. S., & da Fonseca, R. F. (2021). Laboratório de física moderna: análise do efeito hall através do cristal de germânio tipo positivo e tipo negativo Modern physics laboratory: hall effect analysis using positive and negative germanium crystal. Brazilian Journal of Development, 7(6), 54609-54622.

Zucchini, R. R. (2018). Uma estimativa do efeito das incertezas dos padrões na incerteza das curvas de calibração em química analítica. Revista IPT: Tecnologia e Inovação, 2(7).

Published

11/09/2022

How to Cite

SANTOS, R. B.; LEMOS, D. G. de L.; BRANDÃO, Y. F. F.; LIMA FILHO, H. J. B. de . Calibration, automation and control of a Hall effect flow sensor for a distillation column . Research, Society and Development, [S. l.], v. 11, n. 12, p. e198111234359, 2022. DOI: 10.33448/rsd-v11i12.34359. Disponível em: https://rsdjournal.org/index.php/rsd/article/view/34359. Acesso em: 27 apr. 2024.

Issue

Section

Engineerings